                       The APC serial protocol

(extracted from apcd.h)


A few words regarding the APC serial protocol

Firstly, the cable:

You will need a simple 3 wires cable connected as follows:

PC (9 pin)     APC
 2 RxD          2
 3 TxD          1
 5 GND          9

Communication protocol which is used for controlling the APC SmartUPS
is very simple ASCII protocol.
The serial communication is 2400 Bd, 8N1

Basically, your computer send a character to the UPS and UPS answer
with the requested information in the form of the ASCII string terminated
with CR/LF.
In some cases, the UPS answer is the action like battery test etc.

There are two exceptions. If the UPS is switching to the battery, the
characters "!!" are sent to the computer. If the UPS is switching back
on-line, the charater '$' is sent to the computer. If battery is low,
'%' is sent to the computer. When battery is recharged to more than 15%,
'+' is sent to the computer.

The protocol description is not based on informations obtained from APC.
I tried to analyse the protocol on RS-232 port, so my description
is not complete.

Command are:

	SEND			ANSWER

	f			Battery status in %   100 = fully loaded
	N			Line minimum voltage (V)
	M			Line maximum voltage (V)
	Q			Status byte 8 bits long.
                             - 08  On-line LED ON
                             - 10  On Battery LED ON
                             - 18  Both LEDs ON
                             - 02  UPS in shut down state, waiting for AC                  

                             0 - If 1, UPS is in calibration
                             1 - If 1, UPS is sleeping
                             2 -  
                             3 - If 1, AC is here
                             4 - If 1, UPS is running on battery
                             5 -
                             6 - If 1, Battery is low
                             7 - 


	P			UPS load (VA)
	F			Line frequency (Hz)
	L			Line voltage (V)
	O			Output voltage (V)
	C			Inside temperature (Celsius degrees)
	B			Battery voltage


Some signals for UPS control

	Y                       Attention
	W			Switch on battery
	X			Switch back on-line
	A			Lights test
	U			Power failure test
	c			UPS identification ???

One very special signal

	Z ~1500ms pause Z	Switch off the UPS completely and imediately


Special thanks to Kevin D. Smolkowski (kevins@tigger.oslc.org)
 who observed other control codes

     D                       Runtime calibration   ON/OFF
     V                       Firmware revison
     c                       UPS Identification
     k                       UPS Warning (Power Fail, Power Fail + 30,
                                 Low Battery, OFF 
     l                       Low transfer point
     m                       Manufacture date
     n                       UPS serial number
     o                       Nominal UPS output
     p                       UPS turn off delay "020" "180" "300" "600" Cycles
     q                       Low battery signal time "02" "05" "07" "10" Cycles
     r                       Wakeup Delay
     s                       Sensitivity "H" "M" "L"
     u                       High transfer point
     x                       Battery replacement date
     y                       Brand "(C) APCC"
     7                       Option switch settings (Hex) 0F 0E 0C 08 00
     
     -                       Change prev. settings

                             To change UPS name   c - /n newname /n


Further codes, not fully tested

     S                       Soft shutdown, UPS will go back on-line when AC
                                is back
     @222                    Soft shutdown, UPS will NOT go back when AC is back
     U                       Power failure test
     G                       Return 'T' if there was a power failure 
                             Return 'S' if there was not a power failure
                             UPS Test will reset the value to the 'S'
     K 1500ms pause K        Switch off UPS completely after delay